Macey's Electrical - Servicing Electrical Utilities - A complete Network of Quality Equipment  
VLF and Cable Diagnostics Primary and Secondary Current Oil Testing Resonant and Impulse Test  
Insulation Test Cable and Fault Location High Voltage Transformer Test  

  Home | About Us | Contact Us | Site Map | All Products |
                                                                                   | b2 High Voltage | VLF High Voltage HVA Series | HVA34

   

HVA34
VLF High Voltage Test Set
  Product Links
 
  VLF High Voltage HVA Series
  Tangent Delta TD Series
  Partial Discharge PD Series
  Oil Testing - BA Series
 
 
 
   HVA34 Specifications
  
 
  
 
   Additional Features
 
  ●  Dual Discharge Device (DDDŽ),
  ●  integrated electronic and
      mechanical discharge devices
  ●  Easily exchangeable HV cable
  ●  Intuitive menu operation
  ●  Sheath Fault Locating
      (in combination with Earth Fault
      Locator) (not included)
  ●  Vacuum Bottle Test Insulation
      Testing
 
 

Overview
.The compact design and unmatched high voltage output power to weight ratio of the HVA test sets are second to none in the market, and make the b2 electronic high-voltage generators the lightest in all classes at all voltage levels
. Dry system: the HVA34 test set is a dry type test system, have no oil filled components. This means less maintenance, compact and lightweight design and no limitation of operating time. Safety: The instrument has two independent earthing devices (electronic and mechanical discharging) and a 12 kV feedback protection system to protect both operator and instrument.

 
   

Features
 
   ●  Output voltage 29 kVpeak , 21 kVrms
   ●  Pure sinusoidal output voltage (load-independent)
   ●  Internal TD measurement with high accuracy (1 x 10-4)
   ●  Tan Delta measurement with various frequencies (0.01-0.1 Hz)
   ●  Leakage GuardŽ -
   ●  leakage current correction
   ●  Output current 20 mA max.
   ●  0.5 μF @ 0.1 Hz @ 20 kV rms
   ●  Highest test capacity of 10 μF
   ●  Ultra light and compact weight (14 kg
 
 
 

Connectivity: on site, no external PC is needed. All results can be downloaded later by USB for further investigation and easy report creation on the PC software. Solid HV connectors: robust HV-connectors allow the use of different HV test lead lengths, the quick exchange for a replacement cable, or the simpler upgrade path for connection of diagnostics systems. Unlimited operating time: Operating time of the HVA high voltage generators are not thermally limited and can be operated continuously.
 

 
Global Thinking - Local Action    
 

  Our Partners -- Your links to our Quality Products