Technical Specification
AC Flash / Hipot Test

Voltage Range

0.10kV to 5.00kV  Programmable (10V / Step Resolution)

Frequency Independent of Supply

50Hz or 60Hz

Voltage Accuracy

1% of reading 5 Counts

Voltage Resolution

0.01kV

Current Range

0.01mA to 20.00mA

Current Accuracy

1% of reading 5 Counts

Current Resolution

0.01mA

Selectable Range of Pass / Fail Levels

0.01mA to 20.00mA

Maximum Output Current

20mA at 5kV

Arc Detection

9 Levels

 

DC Flash / Hipot Test

Voltage Range

0.10kV to 6.000kV (programmable)

Voltage Resolution

10V / step (settable)

Voltage Accuracy

1% of reading 5 Counts

Voltage Resolution

0.01kV

Maximum Output Current

10mA at 6kV

Current Range

0.01mA to 10.00mA

Current Accuracy

1% of reading 5 Counts

Current Resolution

0.01mA

Selectable Range of Pass / Fail Levels

0.01mA to 10.00mA

Maximum Output Current

10mA

Arc Detection

9 Levels

 

DC Insulation Resistance

DC Voltage Output

250V, 500V or 1000V selectable

Resistance Measurement Ranges

0.01MΩ to 500MΩ

Resistance Accuracy

5% of reading, 5 Counts (0.03MΩ to 350MΩ, 350MΩ to 500MΩ (indication only)

 

Earth / Ground Bond

Test Voltage

6 V AC nominal

Frequency Independent of Supply

50Hz or 60Hz

Measurement Range

0Ω to 1500mΩ, 2% of reading 5 Counts

Display Resolution

1mΩ

Compliance Test Ranges

5A / 1000mΩ / Continuous

10A / 500mΩ / Continuous

25A / 200mΩ / Continuous

30A / 150mΩ / 60 seconds

40A / 100mΩ / 60 seconds

Settable Output Current Range

0.1A to 40A

Selectable Range of Pass / Fail Levels

0Ω to 1500mΩ

 

Power and Leakage Test

Power Output Rating Test Voltage

110V to 230V AC 20A nominal (Vin-Vout)

Maximum Power Output

Up to 5.0kVA (dependant on mains supply rating)

 

Output Power Measurement

Single Phase Power Range

0.02kVA to 5.00kVA

Accuracy

2% of reading 0.02kVA

Selectable Range of Pass / Fail Levels

0.001kVA to 5.000kVA

 

Single Phase Power Factor Measurement

Measurement Range and Accuracy

0.000 to 1.000 0.030

Selectable Range of Pass / Fail Levels

0.000 to 1.000

 

Leakage Current Measurement

Leakage Current Range

0.10mA to 20mA, 1% of reading 5 Counts

Display Resolution

0.01mA

Selectable Range of Pass / Fail Levels

0.01mA to 20mA

 

Touch Current Measurement

Display Range and Accuracy

0.02mA to 5.00mA, 1% of reading 5 Counts

Display Resolution

0.01mA

Selectable Range of Pass / Fail Levels

0.02mA to 5.00mA

 

Environmental

Operating Temperature

0C to 40C

Storage Temperature

-10C to 60C

Humidity

< 75% R.H. non-condensing

 

Safety / EMC

Electrical Safety

IEC 1010-1; CAT II 300V

Pollution

Degree II

RFI Susceptibility

3-volts as per IEC 1000-4-3

Radiation

EN 61326-1-1998 (Class A)

ESD

IEC 801-4

 

General Specifications

Display

1/4-inch VGA Monochrome Graphical

Power Supply

103V to 126V / 207V to 253V AC RMS 50/60Hz (AC input switchable)

Dimensions

300mm (H) x 200mm (W) x 370mm (L)

Weight

15kg approx.

 